Utilities Modules

Black Utilities Module

Black Utilities Module

This specific module includes Black Utilities storage + Distribution systems. 

  • There are 2 kinds of black utilities for SAMPU systems:

    • Cold Water (CW).

    • Compressed Air (CA).

  • Concerning generation, SAMPU system can integrate with existing equipment. If needed, SAMPU can also provide these generation equipment as a complement.


Module’s general characteristics as per Base Clean Room Module

  • Dimensions:

    • External: 5,84 m x 2’35 m x 2’6 m (Length x Width x Height).

    • Internal: 5,72 m x 2’23 m x 2’5 m (Length x Width x Height).

  • Non-classified area.

Cold Water (CW)

  • CW is used for:

    • To cool down the temperature of the product inside the reactors.

    • Regulate the HVAC air conditioning.

    • To cool down the temperature of the PW loop.


  • CW is used on:

    • Manufacturing Module.

    • Holding Reactor Module.

    • HVAC Module.

    • Clean Utilities Module.


  • CW station includes:

    • 1000 l tank, to store externally produced CW:

      • Made of stainless steel 304.

      • Level measurement.

      • Insulated.

    • Pump couple, to keep the loop always moving:

      • 2x pumps in parallel, working in shifts.

      • Automatic switching between pumps.

      • 22.000 l/h at 2,5 barg.

    • Expansion Tanks.

    • Flow, pressure and temperature monitoring.


  • CW is kept and distributed using a closed loop:

    • Starts on the tank.

    • Traverses all the modules where CW is needed through the technical space (see details here).

    • Ends on the tank.

    • Water is always in movement. To ensure a well-functioning of the loop, it is provided with:

      • Balancing Valves.

      • Y-Filters.

      • Expansion Tanks.

      • Automatic Purges.

Compressed Air (CA)

  • CA is used for:

    • To be converted into PCA.

    • To operate pneumatic devices such as valves or pistons.


  • CA is used on:

    • Manufacturing Module.

    • Holding Reactor Module.

    • Sampling Area Module.

    • Weighing Area Module.

    • Filling Module.

    • Feeding Bottles Module.

    • Labelling Module.

    • Automatic Cartoning Module.

    • Case Module.

    • Washing and Storage Module.

    • Laboratory Module.

    • HVAC Module.

    • Clean Utilities Module.

    • Black Utilities Module.


  • CA station includes:

    • Flow monitoring.

    • 1000 l tank.

      • Made of inox 304.

    • Pressure regulation valve + filter.

    • Pressure monitoring.

Design and Manufacturing criteria

  • All pipes in contact with black utilities:

    • Made of stainless steel 304. 

    • Pressure tested.

    • No threaded connections.

  • Black Utilities systems can run autonomously 24/7 without human intervention.

  • According to regulations:

    • European Commission Vol. 4 EU Guidelines to Good Manufacturing Practice. Medicinal Products for Human and Veterinary Use. 

    • Good Manufacturing Practices of the Food and Drug Administration (FDA).

    • 21 CFR Part 11 “Electronic Records, Electronic Signatures”. Food and Drug Administration Title 21 of the Code of Federal Regulations. 

    • Equipment Directive 2006/42/EC.

    • EN ISO 14122: Safety of machinery - Permanent means of access to machinery, part 1 till 4. 

    • EN ISO 13849: Safety of machinery - Safety-related parts of control systems.

HMI

  • Centralized HMI to monitor and control all the stations of Black Utilities Module.

  • Information retained with data integrity complying with CFR 21 Part 11.

  • Prepared to generate:

    • Batch report.

    • Alarms report.

    • Audit trail report.

  • Remote connection for aftersales services.

Documentation

  • Design documentation.

  • DQ protocol + report.

  • As-built documentation:

    • CE Declaration of Conformity.

    • Layouts.

    • Electrical diagram.

    • Pneumatic diagram.

    • Datasheet of valves and/or instrumentation and components.

    • Calibration Certificates.

    • Operation manual:

      • Start-up procedure.

      • Format changeover procedure.

      • Cleaning procedure.

      • Alarms list with every troubleshooting.

    • Maintenance manual.

    • Spare parts list and fungible assets.

  • FAT & SAT protocols + report.

  • IQ & OQ protocols + report.

  • PQ protocol + report.


The standard language of all documentation will be English.